Ficha de datos
- Isolation
- 2 kV (I models)
- 10/100BaseT(X) Ports (RJ45 connector)
- 2 (1 IP, Ethernet cascade) Auto MDI/MDI-X connection
- Magnetic Isolation Protection
- 1.5 kV (built-in)
- Configuration Options
- Web Console (HTTP/HTTPS), Device Search Utility (DSU), MGate Manager, Telnet Console
- Industrial Protocols (Ethernet Software)
- Modbus TCP Client (Master), Modbus TCP Server (Slave)
- Industrial Protocols
- Modbus RTU/ASCII Master, Modbus RTU/ASCII Slave
- Management
- ARP, DHCP Client, DNS, HTTP, HTTPS, SMTP, SNMP Trap, SNMPv1/v2c/v3, TCP/IP, Telnet, UDP, NTP Client
- MIB
- RFC1213, RFC1317
- Time Management
- NTP Client
- Serial Standards
- RS-232/422/485 (software selectable)
- No. of Ports
- 2
- Baudrate
- 50 bps to 921.6 kbps
- Parity
- None, Even, Odd, Space, Mark
- Data Bits
- 7, 8
- Stop Bits
- 1, 2
- Flow Control
- DTR/DSR, RTS Toggle (RS-232 only), RTS/CTS
- RS-485-2w
- Data+, Data-, GND
- Power Connector
- 7-pin terminal block
- Input Voltage
- 12 to 48 VDC
- Weight
- 380 g (0.84 lb)
- Housing
- Plastic
- Operating Temperature
- -40 to 75°C (-40 to 167°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
- Freefall
- IEC 60068-2-32
- EMC
- EN 55032/24
- Safety
- EN 60950-1, UL 508
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV IEC 61000-4-5 Surge: Power: 2 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF IEC 61000-4-11 DIPs
- Shock
- IEC 60068-2-27
- Vibration
- IEC 60068-2-6, IEC 60068-2-64
- Time
- 1,236,384 hrs
- Standards
- Telcordia SR332
- Warranty Period
- 5 years
- Connector
- 2 x DB9 male
- Optical Fiber
- Read More
- Input Current
- 510 mA @ 12 VDC
- IP Rating
- IP30
- Hazardous Locations
- ATEX, Class I Division 2, IECEx If you need an IECEx certificate for this product, please contact a Moxa sales representative.
- Maritime
- DNV-GL
- Max. No. of Client Connections
- 32
- Contact Current Rating
- Resistive load: 1 A @ 30 VDC
- RS-232
- TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
- RS-422
- Tx+, Tx-, Rx+, Rx-, GND
- RS-485-4w
- Tx+, Tx-, Rx+, Rx-, GND
- Dimensions (with ears)
- 29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.90 in)
- Dimensions (without ears)
- 29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in)
- Pull High/Low Resistor for RS-485
- 1 kilo-ohm, 150 kilo-ohms
- RS-485 Data Direction Control
- ADDC® (automatic data direction control)
- Terminator for RS-485
- 120 ohms
- Max. No. of Server Connections
- 32