ioLogik E1214-T
Universal I/O, 6 DIs, 6 relays, -40 to 75°C operating temperature
Universal I/O, 6 DIs, 6 relays, rango de temperatura de -40°C a 75°C
Ficha de datos
- Buttons
- Reset button
- Isolation
- 3k VDC or 2k Vrms
- I/O Mode
- DI or event counter
- Pulse Output Frequency
- 0.3 Hz at rated load (max.)
- Sensor Type
- Dry contact Wet Contact (NPN or PNP)
- LED Indicators
- Power, Ready, Port 1, Port 2
- 10/100BaseT(X) Ports (RJ45 connector)
- 2, 1 MAC address (Ethernet bypass)
- Magnetic Isolation Protection
- 1.5 kV (built-in)
- Configuration Options
- Web Console (HTTP), Windows Utility (ioSearch)
- Industrial Protocols
- Modbus TCP Server (Slave), Moxa AOPC (Active Tag), MXIO Library, EtherNet/IP Adapter
- Management
- RESTful API, SNMPv1/v2c, SNMPv1 Trap, HTTP, DHCP Client, BOOTP, IPv4, TCP/IP, UDP
- MIB
- Device Settings MIB
- Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16, 23
- Mode
- Adapter
Server - Power Connector
- Screw-fastened Euroblock terminal
- No. of Power Inputs
- 1
- Input Voltage
- 12 to 36 VDC
- Power Consumption
- 188 mA @ 24 VDC
- Dimensions
- 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
- Weight
- 200 g (0.44 lb)
- Installation
- DIN-rail mounting, Wall mounting
- Wiring
- I/O cable, 16 to 26 AWG Power cable, 12 to 24 AWG
- Housing
- Plastic
- Operating Temperature
- -40 to 75°C (-40 to 167°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
- Altitude
- 4000 m
- Freefall
- IEC 60068-2-32
- EMC
- EN 55032/24, EN 61000-6-2/-6-4
- Safety
- UL 508
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF
- Shock
- IEC 60068-2-27
- Vibration
- IEC 60068-2-6
- Green Product
- RoHS, CRoHS, WEEE
- Time
- 808,744 hrs
- Standards
- Telcordia SR332
- Warranty Period
- 2 years
- Connector
- Screw-fastened Euroblock terminal
Screw-fastened Euroblock terminal - Hazardous Locations
- ATEX, Class I Division 2
- Digital Input Channels
- 6
- Counter Frequency
- 250 Hz
- Digital Filtering Time Interval
- Software configurable
- Dry Contact
- On: short to GND Off: open
- Points per COM
- 6 channels
- Wet Contact (DI to COM)
- On: 10 to 30 VDC Off: 0 to 3 VDC
- Security
- Access control list
- Max. No. of Client Connections
- 10
- Max. No. of Scanner Connections
- 9 (for read-only), 1 (for read/write)
- Relay Channels
- 6
- Breakdown Voltage
- 500 VAC
- Contact Resistance
- 100 milli-ohms (max.)
- Electrical Endurance
- 100,000 operations @ 5 A resistive load
- Initial Insulation Resistance
- 1,000 mega-ohms (min.) @ 500 VDC
- Mechanical Endurance
- 5,000,000 operations
- Note
- Ambient humidity must be non-condensing and remain between 5 and 95%. The relays may malfunction when operating in high condensation environments below 0°C.
- Contact Current Rating
- Resistive load: 5 A @ 30 VDC, 250 VAC, 110 VAC
- Type
- Form A (N.O.) power relay
- Security Functions: Authentication
- Local database
- Relays: I/O Mode
- Relay or pulse output
No hay ninguna opinión por el momento.