ioLogik E1214-T

Universal I/O, 6 DIs, 6 relays, -40 to 75°C operating temperature

Cantidad

Universal I/O, 6 DIs, 6 relays, rango de temperatura de -40°C a 75°C

Ficha de datos

Buttons
Reset button
Isolation
3k VDC or 2k Vrms
I/O Mode
DI or event counter
Pulse Output Frequency
0.3 Hz at rated load (max.)
Sensor Type
Dry contact Wet Contact (NPN or PNP)
LED Indicators
Power, Ready, Port 1, Port 2
10/100BaseT(X) Ports (RJ45 connector)
2, 1 MAC address (Ethernet bypass)
Magnetic Isolation Protection
1.5 kV (built-in)
Configuration Options
Web Console (HTTP), Windows Utility (ioSearch)
Industrial Protocols
Modbus TCP Server (Slave), Moxa AOPC (Active Tag), MXIO Library, EtherNet/IP Adapter
Management
RESTful API, SNMPv1/v2c, SNMPv1 Trap, HTTP, DHCP Client, BOOTP, IPv4, TCP/IP, UDP
MIB
Device Settings MIB
Functions Supported
1, 2, 3, 4, 5, 6, 15, 16, 23
Mode
Adapter
Server
Power Connector
Screw-fastened Euroblock terminal
No. of Power Inputs
1
Input Voltage
12 to 36 VDC
Power Consumption
188 mA @ 24 VDC
Dimensions
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight
200 g (0.44 lb)
Installation
DIN-rail mounting, Wall mounting
Wiring
I/O cable, 16 to 26 AWG Power cable, 12 to 24 AWG
Housing
Plastic
Operating Temperature
-40 to 75°C (-40 to 167°F)
Storage Temperature (package included)
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
5 to 95% (non-condensing)
Altitude
4000 m
Freefall
IEC 60068-2-32
EMC
EN 55032/24, EN 61000-6-2/-6-4
Safety
UL 508
EMI
CISPR 32, FCC Part 15B Class A
EMS
IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 2 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF
Shock
IEC 60068-2-27
Vibration
IEC 60068-2-6
Green Product
RoHS, CRoHS, WEEE
Time
808,744 hrs
Standards
Telcordia SR332
Warranty Period
2 years
Connector
Screw-fastened Euroblock terminal
Screw-fastened Euroblock terminal
Hazardous Locations
ATEX, Class I Division 2
Digital Input Channels
6
Counter Frequency
250 Hz
Digital Filtering Time Interval
Software configurable
Dry Contact
On: short to GND Off: open
Points per COM
6 channels
Wet Contact (DI to COM)
On: 10 to 30 VDC Off: 0 to 3 VDC
Security
Access control list
Max. No. of Client Connections
10
Max. No. of Scanner Connections
9 (for read-only), 1 (for read/write)
Relay Channels
6
Breakdown Voltage
500 VAC
Contact Resistance
100 milli-ohms (max.)
Electrical Endurance
100,000 operations @ 5 A resistive load
Initial Insulation Resistance
1,000 mega-ohms (min.) @ 500 VDC
Mechanical Endurance
5,000,000 operations
Note
Ambient humidity must be non-condensing and remain between 5 and 95%. The relays may malfunction when operating in high condensation environments below 0°C.
Contact Current Rating
Resistive load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Type
Form A (N.O.) power relay
Security Functions: Authentication
Local database
Relays: I/O Mode
Relay or pulse output

No hay ninguna opinión por el momento.